Temptek Chiller Specifications
8.3 INHIBITED PROPYLENE GLYCOL
To operate liquid chillers below 48°F, it is necessary to add inhibited propylene glycol to the circulating system to lower the freeze point and prevent damage to the cooling system. Inhibited propylene glycol contains corrosion inhibitors which are compatible with most industrial heat transfer surfaces. Inhibited propylene glycol is manufactured by:
• Dow Chemical - “DowFrost” (1-800-258-2436) • Monsanto “Therminol FS” (1-800-459-2665)
• Temptek “Thermofluid” (1-317-887-0729)Automotive anti-freeze must never be used in industrial heat transfer applications. Automotive anti-freeze contains silicate type corrosion inhibitors designed to be compatible with automotive components. In an industrial application, the silicates will form a gel on the heat transfer surface which will result in substantial reduction in cooling capacity and is virtually impossible to remove.
So, a 50F limit would be safe for a water only system. With the glycol that we are using, we are safe in any current operating scenario.
If the ambient temperature goes below 38F, then there are pressure switches that will be triggered.
If the ambient temperature gets too high (an unspecified upper limit, but likely >95F - which is what we hit in the UT lab without failure) then the safety shutdown is triggered.
3ton Temptek Manual PDF
Temptek Manual PDF - 1ton lab chiller
Vacuum Station Manual PDF
Helium Compressor Manual PDF
Cryodyne 1050 Coldhead Manual PDF
Lakeshore 350 Temperature Controller PDF
Lakeshore 332 Temperature Controller PDF
CTI Decontamination Procedures PDF
Decon Procedure_Rev C PDF
.
Welcome to the University Wiki Service! Please use your IID (yourEID@eid.utexas.edu) when prompted for your email address during login or click here to enter your EID. If you are experiencing any issues loading content on pages, please try these steps to clear your browser cache.